Metal collection tray for 3 x 1000 LT IBC tanks - RAL 6011
Metal collection tray for 3 x 1000 LT IBC tanks - RAL 6011
Product Description
| ART. | A | B | C | D | E | Capacity |
| SVR3C | 3434 | 1340 | 330 | 100 | 430 | 3 1000 Lt tanks |

A=Length
B=Width
C=Useful height
D=Foot height
E=Total height
The measurements are expressed in millimeters
General information
Designed to safely contain 3 x 1000 litre IBC containers , the Mayermoover tank in RAL 6011 (reseda green) combines structural efficiency, durability and a discreet, professional aesthetic, suitable for any type of operating context.
Ideal for companies that handle hazardous or polluting liquids, it is designed for environments where environmental safety and orderly container management are a priority.
Solid structure and easy maintenance
The tank is made of 3 mm (30/10) thick S235JR carbon steel , welded using electronically controlled techniques to ensure maximum watertightness . The hot-dip galvanized and completely removable grating simplifies cleaning and maintenance operations, even in environments with intensive use.
The frame is reinforced to support three 1000-litre IBC tanks without deformation, even when fully loaded.
All the materials used are traceable and certified according to UNI EN ISO 9001 , while production follows the UNI reference parameters .
Technical features
-
Capacity: 3 x 1000 litre IBC tanks
-
Material: S235JR or higher carbon steel
-
Thickness: 3 mm
-
Painting: epoxy powder RAL 6011 (reseda green)
-
Hot-dip galvanized and removable grilles
-
Electronically controlled welding
-
Provision for forklift forks
-
UNI regulatory compliance
-
Certifications available upon request
Available upon request
-
Other finishes: hot or cold galvanizing, liquid painting
-
Any RAL color (to be agreed upon based on quantities)
Ideal for
-
Chemical and pharmaceutical companies
-
Logistics, agricultural and manufacturing sectors
-
Environments subject to environmental regulations
-
Contexts where a technical and tidy green finish is useful
Storage and Retention Guide
What does the law say?
According to Legislative Decree 19/05/1999 n. 152 , amended by Legislative Decree 2000 n. 258 , containment basins must have a minimum capacity at least equal to the largest of the stored containers and in any case not less than 1/3 of the total volume of the hazardous substances present. In areas subject to groundwater protection, the legislation instead requires that the entire stored volume be contained within the collection tank ( 100% of the volume ).
⚠️ Attention:
This regulation does not apply to the storage of used oil , for which the law expressly requires a containment tank equal to 100% of the stored volume , regardless of other considerations.
To better clarify the practical application of these rules, we report below two examples with explanatory data:
| Parameter | Example 1 | Example 2 |
|---|---|---|
| Total substances stored | 1500 liters | 3600 liters |
| 1/3 of the total | 500 liters | 1200 liters |
| Larger container | 700 liters | 1000 liters |
| Minimum capacity required | 700 liters (being 700 > 500) |
1200 liters (being 1000 < 1200) |