Product Description

ART. A B C D E Capacity
SVR3C 3434 1340 330 100 430 3 1000 Lt tanks

A=Length
B=Width
C=Useful height
D=Foot height
E=Total height
The measurements are expressed in millimeters

General information

The Mayermoover collection tank for 3 1000-litre IBC tanks , in hot-dip galvanised version, is designed to guarantee maximum resistance to corrosion , even in external or aggressive environments, where humidity and chemical agents can compromise the life of traditional materials.

Made from 3mm carbon steel and protected with integral hot-dip galvanisation, it offers a robust solution, compliant with European regulations, for the containment and safe storage of hazardous and polluting liquids.

Long-term reliability and durability

The tank is equipped with removable, hot-dip galvanized grids for easy maintenance and maximum hygiene. The welds are electronically checked to ensure absolute watertightness. The reinforced load-bearing structure ensures stability even when fully loaded , supporting up to three 1000-liter tanks.

All materials used are UNI EN ISO 9001 certified and meet UNI standards for size and performance.

Technical features

  • Capacity: 3 x 1000 litre IBC tanks

  • Material: S235JR or higher carbon steel

  • Thickness: 3 mm (30/10)

  • Finish: hot-dip galvanizing

  • Grating: hot-dip galvanized, removable, pressed

  • Welding: electronic control for watertightness

  • Handling: forklift ready

  • Production compliant with UNI regulations

  • Material certifications available upon request

Advantages of the galvanized version

  • Maximum protection against corrosion and atmospheric agents

  • Long life even in uncovered industrial environments

  • No need for repainting

  • Ideal for environments with high frequency of washing or chemical exposure

Recommended applications

  • Chemical, petrochemical, logistics sectors

  • External warehouses or coastal areas

  • Industrial systems with high-pressure washing

  • Companies subject to strict environmental controls

Storage and Retention Guide

What does the law say?
According to Legislative Decree 19/05/1999 n. 152 , amended by Legislative Decree 2000 n. 258 , containment basins must have a minimum capacity at least equal to the largest of the stored containers and in any case not less than 1/3 of the total volume of the hazardous substances present. In areas subject to groundwater protection, the legislation instead requires that the entire stored volume be contained within the collection tank ( 100% of the volume ).

⚠️ Attention:
This regulation does not apply to the storage of used oil , for which the law expressly requires a containment tank equal to 100% of the stored volume , regardless of other considerations.

To better clarify the practical application of these rules, we report below two examples with explanatory data:

Liquid containment diagram
Parameter Example 1 Example 2
Total substances stored 1500 liters 3600 liters
1/3 of the total 500 liters 1200 liters
Larger container 700 liters 1000 liters
Minimum capacity required 700 liters
(being 700 > 500)
1200 liters
(being 1000 < 1200)